One package to meet the new NFPA 14 Supervisory Air Requirements.
Per NFPA 14 (2024 edition), all dry standpipe systems—including manual systems—require supervisory air to ensure pipe integrity. General Air Products’ StandGuard™ delivers a fully enclosed, UL-listed digital compressor package designed specifically for fire protection.
With built-in low & high air pressure alerts, excessive run alerts for leak detection, and optional dryer & heated cabinet for unconditioned or cold environments, StandGuard™ is the complete solution for maintaining reliability and compliance in manual dry standpipe systems.
Lead Time: 6 weeks to ship

💡 Did You Know?
Supervisory Air is required on dry standpipe systems per 2024 edition of NFPA 14.
NFPA 14 – 8.3.2.1.1 – “All dry standpipe system piping shall be supervised with supervisory air.”
Additional Downloads
Supervisory Air is required on dry standpipe systems per NFPA 14 (2024) section 8.3.2.1.1 which states, “All dry standpipe system piping shall be supervised with supervisory air.”
Supervisory air is mandated by NFPA 14 (2024) section 8.3.2.1.1 which states, “All dry standpipe system piping shall be supervised with supervisory air.” This standard is to ensure that issues with pipe integrity can be detected and addressed before the system is put into use by the fire department.
Dryers and heaters are not required by NFPA standards. However specific localities, such as New York City, may require them, so be sure to check your local building code before deciding on what optional components you need for your Standguard system.
All General Air Products Standguard units include a standard 1-year manufacturer warranty. Contact us for or refer to product manuals full warranty details.
Replacement parts for Standguard units are available through authorized distributors or directly from General Air Products in the individual product page. Contact technical support at 1-800-345-8207 or through the chat feature in the lower right corner if you need help identifying parts.
If you experience issues with your Standguard unit, contact General Air Products technical support at 1-800-345-8207 or through the chat feature in the lower right corner for expert assistance - from a real live person, we promise 🙂
Features & Benefits
- UL 1450 SC Fire Protection Air Compressor
- UL Listed Digital Pressure Switch
- UL Listed / FM Approved Supervisory Switch
- Lockable Metal Enclosure
- Desiccant Dryer & Automatic Heater (optional)
- Low & High Air Supervisory Alerts
- Excessive Run Alerts for Leak Detection
- Contacts for Easy Connection to Alarm Panel
- Pre-Wired & Pre-Tested
- Lifetime Technical Support